Grey Water System
Grey water is domestic waste water excluding toilet water(sewage) in some instances excludes kitchen water due to organic loading (fats, oils and food etc.).
Bubbler can tailor make systems to treat water for:
- Toilet flushing
- Laundry
- Irrigation
- Pool filling
Existing systems can be converted and upgraded to remove foul odours as well as increase water storage times and capacity.
Grey water systems can be designed to treat from 120L to 10 000L plus .
Systems designed to clients needs and budget requirements.
TECHNICAL SPECIFICATIONS
Tank capacity – Digester Tank : 1400 L / 2200 L / 3600 L.
– Ducting Filter: 270 L
Tank materials: High Density Polyethelene, PVC piping.
SYSTEM FOOTPRINT:
SIZE LENGTH WIDTH HEIGHT
1400L 2.5M 1.6M 1.6M
2200L 2.7M 1.8M 1.4M
3600L 3.6M 2.0M 1.7M
Air pump
Voltage: 220 – 240V.
Frequency: 50Hz.
Power Draw: 100W.
Air Delivery: 140l/min @ 0.042 Mpa.
Liquid Mixing Rate: 118588 L/D @1.7M depth.
Fixed Film Utilization Factor: 37175L/3.19m²/day.
Organic Digestion Rate: 2.7 – 5.4 Kg/BOD/day.
WATER PUMP
Voltage: 220 – 240V.
Frequency: 50 Hz.
Power Draw: 500W.
Flow: 200/300 L/min.
Head: 8/11m